Appendix A Technical Specifications
Multi-Mon Multiple Circuit Energy Monitor
63
Measurement Specifications
Accuracy
AccuracyAccuracy
Accuracy
Parameter
ParameterParameter
Parameter
Full Scale @ Input
Full Scale @ Input Full Scale @ Input
Full Scale @ Input
Range
RangeRange
Range
% Reading
% Reading% Reading
% Reading
% FS
% FS% FS
% FS
Conditions
ConditionsConditions
Conditions
Range
RangeRange
Range
Voltage V
L
= 230V 0.3 0.05 184 to 260 V 0 to Vmax= 600 V
Line current
Instrument current
transformer CTs
I
L
= 100A
0.5 0.05 1 to 100% FS 0 to CT primary current
Starting current: 0.1%
FS
Active power
2 × Vmax × I
L
/1000,
kW
1 0.02
|PF| 0.5
1
-120.000 to 120.000
kW
Reactive power
2 × Vmax × I
L
/1000,
kvar
1 0.02
|PF| 0.9
1
-120.000 to 120.000
kvar
Apparent power
2 × Vmax × I
L
/1000,
kVA
1 0.02
|PF| 0.5
1
0 to 120.000 kVA
Power factor 1.0 - 1.0
|PF| 0.5, I 2% FSI
-0.999 to +1.000
Frequency 0.02 - 50 Hz
50 Hz50 Hz
50 Hz: 39.00 to 65.00 Hz
60 Hz
60 Hz60 Hz
60 Hz: 45.00 to 70.00 Hz
39 Hz up to 70 Hz
Active energy import
4
Class 1.0 under conditions as per IEC 62053-21:2003 0 to 99,999,999.9 kWh
Reactive energy
import/export
Class 1.0 under conditions as per IEC 62053-21:2003,
|PF| 0.9
0 to 99,999,999.9 kvarh
Apparent energy Class 1.0 under conditions as per IEC 62053-21:2003 0 to 99,999,999.9 kVAh
1
@ 80% to 115% of voltage FS and 1% to 100% of current FS
FSV - voltage full scale
FSI - current full scale
Notes
NotesNotes
Notes
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include
inaccuracies introduced by the user's potential and current transformers. Accuracy calculated at 1-second average.
2. Specifications assume: voltage and current waveforms with THD 5% for kvar, kVA and PF; reference operating
temperature: 20°C - 26°C.
3. Measurement error is typically less than the maximum error indicated here.
4. Accuracy of the device without CT complies to IEC 62053-22 class 0.5S standard